When do I need a non-slam check?
High-head pump discharge, long liquid columns, or where swing-check slam has already damaged seats/anchors.
Updated 2026-11-08 · Screening reference — verify against purchaser spec and current standard editions.
Direct answer · Check valve chart
Using this chart on a BOQ? Send size · class/PN · MOC · ends · qty for an Ahmedabad quote.
Contact / RFQ WhatsAppWrong check-valve type is a top cause of water hammer complaints after commissioning. Use this chart before locking the valve type on P&IDs.
| Type | Laying length | ΔP tendency | Slam behaviour | Typical service |
|---|---|---|---|---|
| Swing check | Long (B16.10) | Low–moderate | Can slam on fast reverse | Water, oil, steam utility |
| Dual-plate wafer | Very short | Moderate | Spring-assisted close | CW, fire utility, compact racks |
| Lift / piston | Short–medium | Higher | Better for clean fluids | Small bore, HP instrument/process |
| Ball check | Compact | Moderate | Depends on design | Viscous / slurry-ish (case-by-case) |
| Nozzle / non-slam | Short | Designed low slam | Fast non-slam close | Pump discharge critical |
| Type | Horizontal | Vertical up | Vertical down |
|---|---|---|---|
| Swing | OK | OK if designed | Usually avoid |
| Dual-plate | OK | Confirm spring | Confirm spring |
| Lift | OK | Often preferred | Usually avoid |
| Field | Example |
|---|---|
| Size / Class | 8" Class 150 |
| Type | Dual-plate wafer |
| MOC | WCB body, SS316 plates/springs |
| Ends | Wafer to ASME B16.5 |
| Media / temp | CW water 35°C |
| Slam note | Non-slam preferred / spring assist |
High-head pump discharge, long liquid columns, or where swing-check slam has already damaged seats/anchors.
Not always — debris, coating specs, and purchaser standards may still call swing. Confirm ΔP and laying length.
Yes when type, size, class, MOC and ends are stated via contact.html.