HVAC Chilled Water Valve Chart

Updated 2026-11-08 · Screening reference for engineers & contractors.

Direct answer · HVAC valve chart

Chilled/condenser water loops most often use PN16 wafer or lug butterfly valves with EPDM/NBR seats, plus ball valves on small branches and swing/dual-plate checks on pump discharge. Confirm dead-end lug needs and gear vs lever operators on every line.

RFQ from this chart — size · class/PN · MOC · ends · qty.

Contact / RFQWhatsApp

Building-services contractors lose days when seat material or lug rating is wrong. Lock these fields before tender BOQ freeze.

Typical package

LineValveNotes
CHW mains DN100–600DI/Al butterfly wafer PN16EPDM seat common
Dead-end equipmentLug butterflyRated for one-side removal
Branch ≤DN50Ball valve PN16/Class 150Full bore preferred
Pump dischargeCheck valveSlam note if high head
Isolation + drainBall + hose unionMaintenance

Seat / disc quick picks

PartCommon HVAC pickWatch-out
SeatEPDMNBR for oils; PTFE for chemicals
DiscDI nylon / SSSS for aggressive water
OperatorLever ≤DN150; gear aboveStem extension if insulated

FAQ

Wafer or lug for AHU isolation?

If one flange may be removed, specify lug-rated construction.

UL/FM vs HVAC commercial?

Do not mix fire-listed constructions with commercial HVAC seats unless the listing is required.

Stem extensions?

State insulation thickness on the RFQ.