Why is dirty ΔP much higher?
As the screen blinds, open area falls and K rises sharply. Specify cleaning ΔP (e.g. 0.5–1.0 bar above clean) on the datasheet.
Updated 2026-11-10 · Screening tool · Verify against current standards before design freeze.
Direct answer · What this calculator does
Got a size from this tool? Send type · size · Class/PN · MOC · ends · qty.
Contact / RFQ Quote page WhatsApp| Mesh | Approx opening | Typical duty |
|---|---|---|
| 20 | ~840 µm | Pump suction coarse |
| 40 | ~400 µm | General process |
| 60 | ~250 µm | Instrument / PRV protection |
| 80–100 | ~150–180 µm | Fine filtration upstream of control valves |
As the screen blinds, open area falls and K rises sharply. Specify cleaning ΔP (e.g. 0.5–1.0 bar above clean) on the datasheet.
Process / steam usually flanged RF. Fire / utility may use grooved — confirm listing if fire service.
Upstream of pumps (with care on NPSH), PRVs, meters and control valves. Provide blowdown / drain.
Supreme Valves India supplies constructions by size, rating, MOC and ends. Outputs are screening aids, not certified design.