Duplex Filter Changeover Procedure: Step by Step

Technical guide · Supreme Valves India · Updated 2026-11-21

A duplex filter (duplex strainer) has two filter chambers and a changeover valve, so one chamber can be cleaned while the other stays in service. The changeover itself takes a minute. Most problems come from skipping the steps around it: switching onto a chamber that is empty, or opening a cover that is still under pressure. This is the sequence we give to operators.

When to change over

Do not wait for a flow or pressure alarm downstream. By then the element may already have collapsed or bypassed.

Before you start

  1. Confirm the standby chamber has a clean basket or element fitted, the cover is closed and bolted, and its drain valve is shut.
  2. Check which chamber is in service. The handle or position indicator on the changeover valve points to the chamber in use.
  3. For hot, flammable or toxic fluids, follow the site permit and wear the PPE the fluid requires.

Changeover procedure

  1. Fill and vent the standby chamber. Open the equalising (priming) line if one is fitted, or move the changeover handle just off its seat, and open the vent on the standby chamber. Close the vent when liquid flows without air. Switching onto an air-filled chamber sends a slug of air downstream, which can trip a lube oil pump or starve a burner.
  2. Move the changeover valve slowly and fully to the standby chamber. Flow passes through both chambers during the stroke and is never interrupted. Do not leave the handle in a mid position.
  3. Check the result. Differential pressure should fall back near the clean value and downstream pressure should be steady.
  4. Isolate the dirty chamber. Close the equalising line. The changeover valve now isolates this chamber from the line.
  5. Depressurise and drain. Open the vent on the dirty chamber slowly, then the drain. Wait until the pressure gauge reads zero and the flow from the drain stops.
  6. Open the cover and remove the basket. Loosen cover bolts evenly. If liquid keeps flowing, the changeover valve is passing: stop, close the cover and investigate.
  7. Clean and inspect. Wash or back-flush the basket. Check the mesh for holes and collapsed sections, and the cover O-ring or gasket for damage. Replace anything doubtful.
  8. Refit and leave as standby. Seat the basket properly, close the cover, close the drain, then fill and vent the chamber so it is ready for the next changeover.

Changeover valve arrangements

ArrangementHow it worksWhere it is used
Single-lever plug or ball changeoverOne handle turns linked three-way plugs or balls on inlet and outlet togetherSmall and medium sizes, lube oil and fuel oil skids
Two three-way ball valves with a linkageInlet and outlet three-way valves joined by a common shaft or link barFabricated duplex strainers in process lines
Butterfly valves, usually four, with interlockInlet and outlet valve on each chamber, interlocked so both chambers cannot be shut togetherLarge sizes, cooling water and seawater

With separate butterfly valves, always open the standby chamber fully before closing the dirty one.

Common mistakes

If the changeover valve passes

A small weep from the drain of the isolated chamber means the changeover valve seats are worn or have debris on them. You cannot safely open that chamber with the line under pressure. Plan a shutdown to service the valve, and in the meantime change over more often so that neither basket loads up heavily.

Details to give when ordering a duplex filter

Frequently asked questions

When should a duplex filter be changed over?

When the differential pressure across the in-service chamber reaches the limit in the manufacturer's manual, when the differential pressure indicator or alarm operates, or on a fixed routine for critical lube oil and fuel systems.

Does flow stop during a duplex filter changeover?

No. The changeover valve passes flow through both chambers during the stroke, so supply downstream is continuous.

Why must the standby chamber be vented before changeover?

An empty chamber is full of air. Switching onto it sends a slug of air downstream, which can trip a lube oil pump or upset a burner. Fill and vent the chamber first.

Is it safe to open the dirty chamber while the line is running?

Yes, once the changeover valve has isolated it and it has been depressurised and drained. Confirm zero pressure on the gauge and an open vent before loosening the cover. If liquid keeps flowing, the changeover valve is passing and the cover must stay closed.

What types of changeover valve are used on duplex strainers?

Single-lever linked plug or ball valves on smaller sizes, two three-way ball valves joined by a linkage on fabricated units, and interlocked butterfly valves on large sizes.