Control Valve Rangeability Chart

Updated 2026-11-08 · Equal percentage vs linear vs quick opening.

Direct answer · Characteristic picks

Equal percentage for most variable-ΔP process loops; linear when system ΔP is nearly constant; quick opening for on/off or dump. Typical inherent rangeability for globe equal-percentage trims screens at ~30:1 to 50:1 — confirm on the manufacturer Cv curve and installed gain.

RFQ control valves — size · rating · characteristic · Cv/Kv · actuator · ends · qty.

Contact / RFQ WhatsApp

Inherent flow characteristic comparison

CharacteristicFlow vs travelTypical inherent rangeabilityBest when
Equal percentageEqual % flow change per equal travel step~30:1 – 50:1ΔP falls as load rises (most process)
LinearFlow ≈ proportional to travel~30:1 – 50:1Near-constant ΔP (level, blending)
Quick openingMost Cv early in travelLower useful throttling bandOn/off, dump, relief bypass
Modified / characterized discVendor curveAs publishedButterfly / ball characterized trim

Travel vs relative Cv (schematic %)

Travel %Equal % Cv (rel.)Linear Cv (rel.)Quick opening Cv (rel.)
10~5–8~10~50–70
25~12–18~25~80–90
50~30–40~50~95+
75~55–70~75~98+
100100100100

Relative values are schematic for teaching. Use the published inherent characteristic for the exact trim. Installed characteristic = inherent × system gain from piping ΔP.

Application quick picks

Loop / dutyPreferred characteristicValve types often used
Pressure / flow with varying ΔPEqual percentageGlobe, characterized ball / butterfly
Tank level (constant head)LinearGlobe, butterfly
Steam pressure reducingEqual percentageGlobe (check noise / cavitation)
ESD / dump / open-closeQuick opening or on/offBall, butterfly, gate
Wide turndown processEqual % + verify rangeabilityGlobe with characterized cage

FAQ

What is control valve rangeability?

Rangeability is the ratio of maximum controllable flow to minimum controllable flow (often stated as installed or inherent). Typical globe equal-percentage trims screen around 30:1 to 50:1; confirm on the manufacturer curve.

When do I specify equal percentage vs linear?

Equal percentage is the default for most process loops where ΔP varies with load. Linear is preferred when ΔP is nearly constant (level loops, some blending). Quick opening is for on/off or dump service, not fine throttling.

Does butterfly valve characteristic match globe equal percentage?

A standard butterfly disc is roughly equal-percentage in mid-travel but flattens near full open. Use the published inherent characteristic and installed gain, not a globe assumption.