| OS&Y gate (outside screw & yoke) | Riser / system control valve; sectional isolation where visual stem position is required | Rising stem shows open/closed; often locked open + supervised | Size, flanged or grooved, rating, listing if required |
| NRS gate (non-rising stem) | Pit / underground / height-restricted isolation; post-indicator driven packages | Stem not visible; use indicator post or switch per design | State NRS vs OS&Y explicitly |
| Butterfly — with supervisory (tamper) switch | Compact supervised control / isolation on sprinkler & standpipe | Switch signals unauthorized closure to FACP | Confirm switch included; listing construction if required |
| Butterfly — without supervisory switch | Utility isolation, secondary shut-off, non-supervised branches | Manual only | Do not assume fire-control listing without RFQ confirmation |
| Swing / wafer check | Prevent reverse flow on fire pump discharge, tank fill, city connection | N/A (check) | Orientation, ends, spring-assisted if specified |
| Y-strainer (flanged / grooved) | Protect pumps, deluge / alarm valves, meters from debris | N/A | Mesh, blowdown, body MOC, ends |