What water velocity should I use for process lines?
Typical screening: 1.5–3.0 m/s for pumped process water; cooler suction often lower (0.9–1.5 m/s). Follow the project piping design basis if it differs.
Updated 2026-11-08 · Recommended velocity bands for line sizing screening.
Direct answer · Velocity bands
RFQ from this chart — media · flow · line size · class/PN · MOC · ends · qty.
Contact / RFQ WhatsApp| Service | Typical velocity (m/s) | Typical velocity (ft/s) | Notes |
|---|---|---|---|
| Pump suction (clean water) | 0.9 – 1.5 | 3 – 5 | Limit NPSH risk / swirl |
| Pump discharge / process water | 1.5 – 3.0 | 5 – 10 | Common EPC screening band |
| Cooling water (large mains) | 1.2 – 2.5 | 4 – 8 | Balance ΔP vs pipe cost |
| Fire water (utility / hydrant) | 2.5 – 5.0 | 8 – 16 | Follow NFPA / AHJ hydraulic calc |
| Condensate (gravity / pumped) | 0.6 – 1.5 | 2 – 5 | Avoid flashing erosion at valves |
| Boiler feedwater | 1.5 – 3.5 | 5 – 11 | Check OEM / consultant note |
| Service | Typical velocity (m/s) | Typical velocity (ft/s) | Notes |
|---|---|---|---|
| Saturated steam — distribution | 25 – 40 | 80 – 130 | Screening for mains |
| Saturated steam — short branch | 20 – 30 | 65 – 100 | Lower noise near occupied areas |
| Superheated steam | 30 – 60 | 100 – 200 | Density lower; watch erosion |
| Exhaust / vacuum steam | 15 – 30 | 50 – 100 | Large diameter, low ΔP |
| Steam to trap / drip legs | — | — | Size for condensate load, not steam velocity alone |
Bands are engineering screening only. Freeze on the project design basis, noise criteria and erosion limits. Fire-protection velocities must follow the hydraulic calculation accepted by the authority having jurisdiction.
For water: Q (m³/h) ≈ 2.827 × ID²(mm) × V(m/s) / 1000. For steam, convert mass flow with density at the design P/T before applying velocity. Then size the valve with Cv or Cv↔Kv.
Typical screening: 1.5–3.0 m/s for pumped process water; cooler suction often lower (0.9–1.5 m/s). Follow the project piping design basis if it differs.
Steam density is much lower, so economic line size uses higher velocity. Saturated steam mains commonly screen at 25–40 m/s; superheated may go higher if noise and erosion allow.
High velocity raises erosion, noise and ΔP across globe and butterfly valves. Size the valve for required Cv/Kv at the stated flow, then check seat/trim for the service.