Boiler Blowdown Rate Calculator — Continuous & Intermittent

Updated 2026-11-10 · Screening tool · Verify against current standards before design freeze.

Direct answer · What this calculator does

Continuous blowdown rate BD = F × (TDS_fw / (TDS_max − TDS_fw)) where F is feedwater mass flow. Use the result to discuss CBD globe / angle valves and IBD sequencing — not as a substitute for the boiler OEM calculation.

Got a size from this tool? Send type · size · Class/PN · MOC · ends · qty.

Contact / RFQ Quote page WhatsApp

Blowdown inputs

kg/h
ppm
ppm

Results

Copy into your RFQ or open Contact / RFQ.

Formulas used

BD = F × TDS_fw / (TDS_b − TDS_fw)
F = feedwater kg/h · TDS in ppm · BD in kg/h
% blowdown = 100 × BD / F
Intermittent bottom blowdown is time-based — size valves for short high-velocity discharge with erosion trim
CBD usually takes off near the waterline; IBD from the mud drum. Specify IBR docs when the boiler inspector requires them.
Screening only. TDS limits come from the boiler water treatment programme. Confirm with the water chemist / OEM before freezing valve Cv.

Reference table

StreamTypical valveNotes
Continuous BDGlobe / angleThrottling, flashing risk
Intermittent BDGate / angle / plungerQuick open, erosion trim
Isolation upstreamGateFull bore, IBR as required

How to use the result on an RFQ

  1. Run with your design data.
  2. Record the green outputs.
  3. Paste type, size, Class/PN, MOC, ends, qty into contact or WhatsApp.
  4. Request 3.1 MTC / API 598 notes when required.

FAQ

What if TDS_fw ≥ TDS_max?

Treatment is wrong — blowdown formula breaks down. Fix chemistry first.

Is CBD recoverable?

Often routed through a flash vessel / heat recovery. Valves still see two-phase flow — specify for flashing service.

Do I need two valves in series?

Many codes / practices use dual isolation or a combination of regulating + isolation — follow the boiler package spec.