Blowdown Valve Selection Chart — Intermittent vs Continuous BDV

Updated 2026-11-08 · Boiler water solids control screening. Follow boiler OEM, IBR inspector and purchaser piping class for final selection.

Direct answer · Blowdown valve selection

Intermittent (bottom) blowdown → short, high-ΔP sludge discharge; often tandem angle / slow-open BDVs with hard seats. Continuous (surface) blowdown → throttled conductivity control; needle / multi-stage / characterized globe to flash tank. Do not use ordinary gate valves as BDVs. State boiler P/T, intermittent vs continuous, tandem, flash destination and IBR on the RFQ.

BDV RFQ — intermittent/continuous · size · Class · MOC · hard-face · tandem · IBR · qty.

Contact / RFQ WhatsApp

Blowdown valves see some of the most severe flashing and solids-laden duty on a boiler island. Erosion, wire-drawing and seat leak-by are normal end-of-life modes if the wrong pattern or soft trim is chosen. The tables below separate intermittent vs continuous service and list the RFQ fields inspectors and EPC buyers expect.

Intermittent vs continuous — function matrix

ItemIntermittent (bottom)Continuous (surface)
PurposeRemove sludge / settled solidsControl TDS / conductivity
LocationMud drum / bottom connectionNear waterline / surface take-off
DutyShort open periods (seconds–minutes)Throttled continuous or modulated
Flow characterTwo-phase flash, abrasiveFlashing liquid; steadier
Typical valveAngle BDV, often tandemNeedle / multi-turn globe / orifice + valve
AutomationManual or timedOften conductivity controller
DestinationFlash tank / blowdown vesselFlash tank / heat recovery

Valve pattern recommendations

PatternBest forCaution
Angle blowdown valve (slow open)Intermittent primary wear valveHard-faced seat/disc; replaceable trim
Quick-opening BDVUpstream of tandem pair (where OEM allows)Operate per sequence only
Straight globe (throttling)Continuous BD with hard trimCheck velocity / staging
Needle / fine-controlSmall continuous BD linesPlugging if dirty — strainer upstream
Orifice union + isolationFixed continuous rateOrifice wear changes rate
Gate valveNot for throttling BDIsolation only if class allows — not BD trim
Ball valve (soft seat)Generally unsuitable for hot flash BDSeat damage / flashing

Tandem intermittent blowdown practice

Sequence (typical)ActionReason
1Open upstream (quick) fullyReady path; seats protected
2Open downstream (slow) graduallyDownstream takes wire-draw wear
3Blow for timed durationPer water chemistry / OEM
4Close downstream firstWear valve closes on flow
5Close upstreamIsolates; keeps upstream seats cleaner

Exact sequence can reverse on some OEM manuals — always follow the boiler manufacturer and site SOP. Never leave a single BDV cracked open as a “continuous” substitute.

Pressure class & MOC screening

Boiler design P (screen)Typical ClassBody MOCTrim notes
≤10 kg/cm²g150 / 300WCB / forged CS13Cr / SS; hard-face preferred
10–25 kg/cm²g300 / 600WCB / WC6Stellite / hard-face seat
25–40 kg/cm²g600WC6 / alloyHard-face + erosion design
>40 kg/cm²g600 / 900+Per OEM metallurgySpecial BDV package

Match or exceed boiler design pressure with temperature derating. IBR stamp is commonly required on boiler-connected blowdown valves in India — state this explicitly.

Flash & piping notes

TopicEngineering note
Flash fractionBoiler water at Psat flashes when dropped to flash-tank pressure; volume expands sharply
VelocityTwo-phase velocity drives erosion — short, guided discharge preferred
Silencer / tankDo not discharge occupied areas; use approved blowdown vessel
Heat recoveryContinuous BD often routed via heat exchanger — confirm ΔP for valve sizing
Drain slopeAvoid pockets that cool and hammer on next open

Continuous blowdown control options

MethodHardwareWhen used
Manual needle setNeedle / fine globeSmall boilers, stable load
Fixed orifice + isolationOrifice plate/unionKnown continuous rate
Conductivity controlModulating valve + probePackaged / industrial boilers
Sample cooler circuitSeparate sample valvesChemistry lab — not BDV substitute

RFQ data fields (copy into enquiry)

FieldWhat to writeExample
ServiceIntermittent / continuous / bothIntermittent bottom BD
Boiler design P / Tkg/cm²g and °C21 kg/cm²g / 216 °C sat
SizeDN / NPSDN40
RatingClass or PNClass 300
PatternAngle / globe / needle / tandemTandem angle BDV
Body / trimMOC + hard-faceWCB + Stellite seat
EndsRF / SW / BWFlanged RF
DestinationFlash tank PAtmospheric flash vessel
IBRStamp required?Yes
Docs3.1 / GA / ITPEN 10204 3.1 + API 598
Qty / tagsPer boiler2 sets boiler #1

Related strainer & sample — do not confuse

ItemDutyVs boiler BDV
Y-strainer blow-offClear screenNot for boiler solids control
Level gauge drainGauge glass serviceSmall utility; separate Spec
Sample cooler inletChemistry sampleCool before instruments
IBD / CBD valvesBoiler water chemistryThis chart’s scope

FAQ

What is the difference between intermittent and continuous blowdown?

Intermittent (bottom) blowdown removes sludge from the mud drum / bottom of the boiler in short open periods. Continuous (surface) blowdown skims dissolved solids from near the water surface to hold conductivity. Valve construction, orifice and duty cycle differ; do not substitute a standard isolation gate for either without purchaser approval.

Why are angle valves used on intermittent blowdown?

Angle pattern blowdown valves give a straighter erosion path for flashing two-phase flow, often with hard-faced seats and replaceable discs. Straight globe or gate valves erode quickly under high ΔP flash to atmosphere or flash tank.

Should blowdown valves be installed in tandem?

Many codes and boiler OEMs require two valves in series on intermittent blowdown: one quick-opening and one slow-opening (or two slow), operated in a defined sequence so the downstream valve takes the wear. Follow the boiler OEM and IBR inspector instruction.

What RFQ fields are needed for blowdown valves?

Boiler design pressure and temperature, intermittent vs continuous, size, Class/PN, body/trim MOC, hard-facing, ends, tandem yes/no, flash tank or atmosphere, IBR stamp, and quantity/tags.

Can a Y-strainer blowdown cock replace a boiler BDV?

No. Strainer blow-off cocks are for cleaning the strainer screen only. Boiler blowdown valves are rated and sequenced for boiler water solids control under IBR/OEM rules.

Related charts

Screening guidance for 2026. Verify tandem rules, hard-facing and Class against boiler OEM manuals and current IBR / ASME editions before purchase.