Can I use this flange bolt torque chart for final field torque?
No. These are orientation / screening values only. Final torque must come from the project bolting procedure, gasket manufacturer data, lubricant, and stud grade.
Updated 2026-11-08 · Orientation / screening only — not a site procedure.
Direct answer · Flange bolt torque
Need flanged valves for a bolting package? Send size · class · facing · MOC · qty.
Contact / RFQ WhatsAppAssumptions for the orientation tables: ASTM A193 B7 studs / A194 2H nuts, lubricated threads (typical nut factor K ≈ 0.15–0.18), spiral-wound or CAF-style RF gasket, ambient assembly. Change any of those and the torque changes. For interactive sizing see the flange bolt torque calculator.
| Bolt / stud size | Typical target stress band | Lubricated torque (N·m) | Lubricated torque (ft·lb) | Notes |
|---|---|---|---|---|
| ½" | Screening | 60–90 | 45–65 | Common Class 150 small bore |
| ⅝" | Screening | 120–170 | 90–125 | Class 150 / 300 mid sizes |
| ¾" | Screening | 200–280 | 150–205 | Watch gasket crush on soft CAF |
| ⅞" | Screening | 320–420 | 235–310 | Class 300 / 600 common |
| 1" | Screening | 480–620 | 355–455 | Use calibrated hydraulic / torque tools |
| 1⅛" | Screening | 680–860 | 500–635 | Multi-pass star pattern mandatory |
| 1¼" | Screening | 900–1150 | 665–850 | Often tensioner preferred on critical lines |
| 1½" | Screening | 1600–2000 | 1180–1475 | Confirm with project procedure |
| NPS | Bolts × size | Typical lubricated band (N·m) | Pass sequence cue |
|---|---|---|---|
| 2" | 4 × ⅝" | 120–170 | 30% → 60% → 100% star |
| 3" | 4 × ⅝" | 120–170 | 30% → 60% → 100% star |
| 4" | 8 × ⅝" | 120–170 | Cross pattern; circular finish |
| 6" | 8 × ¾" | 200–280 | Cross pattern; circular finish |
| 8" | 8 × ¾" | 200–280 | Cross pattern; circular finish |
| 10" | 12 × ⅞" | 320–420 | Numbered star; 4 passes typical |
| 12" | 12 × ⅞" | 320–420 | Numbered star; 4 passes typical |
| 16" | 16 × 1" | 480–620 | Consider tensioners on critical service |
| 20" | 20 × 1⅛" | 680–860 | Project procedure governs |
| 24" | 20 × 1¼" | 900–1150 | Project procedure governs |
| NPS | Class 300 bolts | Class 600 bolts | Torque cue |
|---|---|---|---|
| 4" | 8 × ¾" | 8 × ⅞" | Class 600 needs higher band — do not reuse Class 150 torque |
| 6" | 12 × ¾" | 12 × 1" | Bolt diameter jump drives torque up sharply |
| 8" | 12 × ⅞" | 12 × 1⅛" | Verify lubricant and gasket crush load |
| 10" | 16 × 1" | 16 × 1¼" | Hydraulic torque / tensioner common |
| 12" | 16 × 1⅛" | 20 × 1¼" | More bolts + larger size on Class 600 |
| 16" | 20 × 1¼" | 20 × 1½" | Always use purchaser bolting procedure |
| Variable | Effect on wrench torque | RFQ / site note |
|---|---|---|
| Dry vs lubricated | Dry often ~25–40% higher for same tension | State paste / moly / dry in procedure |
| B8 / B8M stainless studs | Lower usable stress; galling risk | Do not copy B7 torque blindly |
| Soft CAF / PTFE gasket | Lower seating stress needed | Easy to crush — lower end of band |
| Spiral wound / RTJ | Higher seating / ring engagement | Follow gasket / ring maker data |
| Hot re-torque | May be specified after heat-up | Only if procedure allows |
Screening data only. Confirm bolt counts against Class 150/300 and Class 600 dimension charts and the current ASME B16.5 edition.
No. These are orientation / screening values only. Final torque must come from the project bolting procedure, gasket manufacturer data, lubricant, and stud grade.
No. Dry threads need significantly higher wrench torque to reach the same bolt stress. Always state lubricant (or dry) in the procedure.
Supreme Valves supplies flanged valves. Field flange assembly torque is set by the piping contractor / EPC bolting procedure, not by the valve datasheet alone.