Download PDF
Supreme Valves India Logo

Supreme Valves India

Ranginwala Building, Relief Road, Ahmedabad 380001, Gujarat, India
Tel: +91 97732 78770 | Email: supremevalvesindia@gmail.com | www.supremevalves.in

Flame Arrester -- End-of-Line & In-Line API 2020

Technical Datasheet -- Crimped Ribbon Flame Arresters for Vent and Pipeline Protection

Document No.SV-DATA-FLA-001
RevisionA
DateMay 2026
ManufacturerSupreme Valves India, Ahmedabad, Gujarat, India

End-of-line and in-line flame arresters for preventing flame propagation in tank vents, process pipelines, and atmospheric discharges. Crimped ribbon or parallel plate SS316 element quenches deflagration and detonation flame fronts by heat dissipation in narrow channels. Housing in carbon steel epoxy-coated or SS316. Element gap matched to gas group (IIB3, IIB, IIA). ATEX / IECEx certified for Zone 0, 1, 2. API 2020 / EN ISO 16852 compliant. Removable element for inspection and replacement.

Technical Specifications
ParameterSpecification
Product TypeFlame Arresters
CategorySafety & Relief Valves
Size Range1/2" to 24" (DN15 to DN600)
Pressure RatingPN10 / PN16 / Class 150 -- up to 40 bar (580 psi) on request
End ConnectionsFlanged RF per EN 1092-1 PN10/PN16 / ASME B16.5 Class 150, Threaded NPT / BSP (small sizes)
Housing MaterialASTM A216 WCB epoxy-coated / ASTM A351 CF8M (SS316) / Aluminium alloy (lightweight, on request)
Element MaterialSS316 crimped ribbon or parallel plate (standard) / Hastelloy C (aggressive chemical) / Aluminium (lightweight, on request)
Gasket MaterialGraphite with SS316 spiral wound / PTFE / RPTFE
Flame TypeDeflagration (subsonic) / Detonation (supersonic) -- element design matched to flame speed group (IIB3, IIB, IIA)
Installation TypeEnd-of-line (vertical or horizontal vent discharge) / In-line (pipeline between protected equipment and ignition source) / Short-time burning / endurance burning
Temperature Range-40 deg C to +150 deg C (standard SS316 element) -- up to +300 deg C (Hastelloy element on request)
Gas GroupIIB3 (ethylene-based gases, MESG >= 0.65 mm) / IIB (MESG >= 0.50 mm) / IIA (MESG >= 0.90 mm) -- element gap matched to gas group
Materials of Construction
ComponentMaterial
Carbon SteelASTM A216 WCB epoxy-coated housing (standard industrial)
Stainless SteelASTM A351 CF8M (SS316) housing and element (corrosive / marine / food-grade service)
Nickel AlloyHastelloy C element (aggressive chemical, chlorine, acid service)
GasketGraphite/SS316 spiral wound (standard), PTFE/RPTFE (chemical service)
Testing & Inspection
TestRequirement
TestingHydrostatic shell test 1.5 x WP per API 598 / EN 12266-1; Seat leakage test per API 598 / EN 12266-1; Functional test -- full stroke, torque; Material certificates per EN 10204 3.1
CertificationISO 9001:2015 QMS, EN 10204 3.1 material certificates, hydrostatic and seat test reports
Applicable Standards
StandardDescription
Design StandardAPI 2020 Flame Arresters in Petroleum Systems, EN ISO 16852 Flame Arresters -- Performance Requirements, Test Methods and Limits for Use, ATEX Directive 2014/34/EU

Notes