Fire-Safe Ball Valves to API 607: What the Test Covers and How to Specify

Technical guide · Supreme Valves India · Updated 2026-10-24

Almost every ball valve specification for refinery, petrochemical, gas and fuel storage service includes the words "fire-safe to API 607". A soft-seated ball valve seals on PTFE or similar seats that will melt in a fire, so the requirement exists to make sure the valve still limits leakage when that happens. This article explains what the fire test proves, how fire-safe designs achieve it, and how to specify it correctly.

What API 607 tests

API 607 is a fire type test for quarter-turn valves and other valves with non-metallic seats. Its current edition is technically aligned with ISO 10497. In outline:

  1. A sample valve is installed closed, filled with water and pressurised.
  2. It is enveloped in flames at a controlled temperature, typically 750 to 1,000 °C measured near the body, for 30 minutes.
  3. Leakage through the seat and to atmosphere (stem and body joints) is measured during the burn.
  4. After cooling, the valve is tested again for seat and external leakage, then operated, and external leakage is measured once more.

The valve passes if leakage stays within the limits in the standard throughout. The test is destructive and done once per design range; it is not a production test on each valve.

How fire-safe ball valves are designed

API 607, API 6FA or ISO 10497?

Reading a fire-safe certificate

Ask for the certificate and check:

A certificate for a floating ball valve does not cover a trunnion design, and a certificate for PTFE seats does not automatically cover PEEK or another seat material.

Where fire-safe valves are specified

Fire protection water systems are a different requirement: there, valves are typically UL Listed or FM Approved for sprinkler and hydrant service, not fire tested to API 607.

RFQ checklist

Send the valve data sheet and we will confirm fire-safe design and certificate coverage for each line item.

Frequently asked questions

Does fire-safe mean the valve will not leak in a fire?

No. It means a valve of that design has passed a standard fire test with leakage through the seat and to atmosphere within set limits, during a burn and after cooling, and could still be operated afterwards. It limits leakage so the fire is not fed; it does not guarantee zero leakage.

What is the difference between API 607 and API 6FA?

API 607 (aligned with ISO 10497) is the fire test for quarter-turn valves and valves with non-metallic seats, used for most plant ball and butterfly valves. API 6FA is the fire test for valves built to API 6A and API 6D, such as wellhead and pipeline valves. Specify the one that matches the valve's design standard or the project specification.

Is a fire-safe certificate needed for every valve size?

No. The fire test is a type test. Each test qualifies a range of sizes and pressure classes of the same design according to the rules in the standard, so the certificate should be checked to confirm it covers the size, class and seat material being supplied.

Related products & guides